Voltage Drop Calculator

  • 120 V
  • 208 V
  • 230 V
  • 240 V
  • 480 V
  • Copper
  • Aluminum
  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG
  • 6 AWG
  • 4 AWG
  • 2 AWG
  • 1/0 AWG
  • 2/0 AWG
  • 4/0 AWG
Results
—
—

The Voltage Drop Calculator estimates the voltage lost along a conductor for a given current, one-way run, and wire size, and flags whether the drop exceeds the 3% guideline. Choose copper or aluminum.

Formula
Vdrop = 2 × K × I × D ÷ CM (K = 12.9 Ω·cmil/ft for copper, 21.2 for aluminum)

FAQ

How much voltage drop is acceptable?
Most electrical codes recommend keeping total voltage drop to about 3% on a branch circuit and 5% from the service to the load.

Embed this calculator on your site

Cite this page

About these results

Every calculation on this page runs locally in your browser using published, standard formulas — nothing you enter is sent to a server. Results are estimates for planning purposes and can differ from real-world conditions; always follow your local building code and the advice of a qualified professional for final decisions. You can read more about who builds and maintains these tools on our About page. About MateCalc.