Rebar Weight Chart — lb/ft & kg/m by Bar Size

A quick reference for the weight of reinforcing steel bars, sizes #3 through #18. Every value below is computed from the bar's cross-sectional area and the density of structural steel — not copied from a catalog — so the numbers are internally consistent and the method is fully transparent. Use it to check deliveries, estimate tonnage, or as a citation for your own project write-up.

How the weight is calculated

A steel bar is a cylinder, so its weight per unit length is just its cross-sectional area times the density of steel:

Formula
Weight per ft = π⁄4 × d² × 12 in × (490 lb/ft³ ÷ 1728)

where d is the nominal bar diameter in inches. This simplifies toWeight (lb/ft) ≈ d² × 2.67. Structural steel is taken at 490 lb/ft³(≈ 7,850 kg/m³), the standard density used throughout ourrebar calculator. Sizes #3–#8 have a nominal diameter of exactly size÷8 inch; #9 and larger use the actual ASTM A615 nominal diameter (which includes the deformation ribs).

Weight per linear foot & meter

Bar sizeNominal dia.
(in)
Nominal dia.
(mm)
Area
(in²)
Weight
(lb/ft)
Weight
(kg/m)
#30.3759.50.1100.3760.559
#40.512.70.1960.6680.994
#50.62515.90.3071.0441.554
#60.7519.10.4421.5032.237
#70.87522.20.6012.0463.045
#8125.40.7852.6733.977
#91.12828.70.9993.4005.060
#101.2732.31.2674.3116.415
#111.4135.81.5615.3137.907
#141.68242.72.2227.56111.252
#182.25757.34.00113.61420.260

Weight per full-length stick

Rebar is commonly delivered in 20 ft or 40 ft sticks. Multiply the lb/ft value by the stick length to get the weight each crew member is actually carrying:

Bar sizelb / 20 ft sticklb / 40 ft stickkg / 12 m length
#37.515.06.7
#413.426.711.9
#520.941.818.6
#630.160.126.8
#740.981.836.5
#853.5106.947.7
#968.0136.060.7
#1086.2172.477.0
#11106.3212.594.9
#14151.2302.4135.0
#18272.3544.6243.1

Estimating grid tonnage

To go from this chart to a real order, you need total bar length. For a slab mat with bars spaced evenly in both directions over an area, a simple estimate is:

Method
Total length ≈ (Area ÷ spacing × 2 directions)  →  Weight = Total length × lb/ft

For example, a 10 × 10 ft pad with #4 bars at 6 in on-center both ways runs ≈ 40 ft each direction (80 ft total) × 0.668 lb/ft ≈ 53 lb of steel — before the usual cutting/waste allowance. For anything structural, don't hand-count: use therebar calculator to size the whole pour, and pair it with thecolumn andslab volume tools to order concrete and steel together.

Not included on purpose: lap-splice, development, and concrete-cover lengths are set by your local building code, concrete strength, and seismic zone — they are not universal numbers, so we don't publish a one-size value here. Confirm them with your engineer or code before building.